Menu
VFDS: ASKING THE RIGHT QUESTION

CSUSA Business Matters
  
Variable Frequency Drives: Asking the Right Questions
  
Key Points
  •  VFDs can save energy, but you may have questions about cost and compatibility issues.
  • Frequently asked questions range from applicability to the potential for bearing or motor failure.
 
In commercial and industrial facilities, the use of variable frequency drives (VFDs) is growing, and for good reason. VFDs can reduce motor electricity usage by 25 to 85 percent, depending on the application. VFDs also minimize wear and tear on motors, reducing maintenance costs and increasing equipment life.
 
Despite these benefits, you may have concerns about cost and compatibility issues. This guide to frequently asked questions about VFDs can help you get the answers you need.
 
What applications are best for VFDs? VFD controls produce the most savings on motors operating at full load a small amount of time (10 to 15 percent), but mostly at less than full load. Varying torque loads where equipment is easy to start and harder to operate at fast speeds are also good candidates. Examples include ventilation fans, water pumps and rotary screw-type air compressors.
 
Do VFDs increase motor efficiency? All motors have lower efficiency at part load, including those with VFDs. VFDs save energy mainly by reducing motor speed — and horsepower — to match demand reductions in the equipment that it's driving — fans, pumps and so on.
 
Will there be a reduction in peak demand? Installing a VFD typically has little or no impact on peak demand. Demand is typically measured in 15-minute increments; the motor's inrush current lasts only a few seconds during startup. However, a VFD can significantly reduce the inrush current, which is typically up to five times the full-load current. Reducing the inrush current helps minimize electrical and mechanical stresses at startup.
 
Can VFDs cause bearing or motor failure? VFDs produce high-frequency voltage pulses that can degrade the insulation on  standard wound motors. Those pulses also produce stray high-frequency currents that can pass through motor bearings, causing  arcing, sparking and pitting. This can result in bearing and motor failure. Adding grounding brushes to the motor shaft will help prevent this problem.
 
Will VFDs result in harmonic problems? In some cases, VFDs cause harmonic distortion in a motor's electric currents, which can result in excessive heating. A number of solutions are available to reduce harmonic distortion, including active and passive harmonic filters, 18-pulse harmonic-reduction drives and active front-end drives. A harmonics analysis of the system can help in selecting the right solution.
 
Are VFDs required for all motors on a multiple pump or fan system? In the case where more than one motor supplies power to one fluid flow (gas or liquid) stream, it is usually best to designate one motor as a trim unit and the remaining motors as baseload units. The trim unit will be controlled by a VFD and bring the flow level up to the baseload motor capacity. Then the non-VFD baseload motor will operate at full rated capacity while the trim unit drops down and smoothly adds capacity up to the simultaneous operation of a  second baseload unit and so on.

  CSUSA Business Matters has been prepared solely for the purpose of providing helpful information to users of this service. The information has be en compiled by Questline, a contractor to Comfort Systems USA; however, no representation is made by either Questline or Comfort Systems USA  as to the completeness or accuracy of  the information contained therein. In particular, some information may be incomplete, may contain errors or may be out of date. In addition, neither Questline nor Comfort Systems USA endorses any product or service mentioned therein.


Stephanie Rainbow, FMP, CFM, SFP
Business Development Manager
(210) 319-9363 Cell


 


PO Box 461085
San Antonio, TX 78246
Need Help With This Site?
© 2024 San Antonio IFMA